Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/04/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN - VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF THE TRAP - DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP - FUSE STAT NOT REQUIRED REMOVE FUSE STAT & PROVIDE ANOTHER RECEPTACLE - INSULATE ANY UNINSULATED DUCT IN FURNACE CLOSET - SECURE THE COPPER DRAIN LINE IN FURNACE CLOSET |