Permit: T08ME00133

Parcel: 136321510


Addresses:

4611 S BAYPORT PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/10/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/03/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAX 30 AMP BREAKER ON #10 CU ROMEX
2) NEED NO/LOX ON AL. CONDUCTORS AT ALL TERMINALS HOT WIRES TO REMAIN BLACK, OR RED
3) REMOVE 60/60 FUSES MARK WHICH SIDE CONTROLS AC, REMOVE EXTRA ?
4) MISSING ROOF JACK AT NEW DISCONNECT
5) NEED BUBBLE COVER ON SERVICE OUTLET
6) BLANK OFF ALL OPEN K.O.'S IN SERVICE PANEL
05/27/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TO MANY CODE VIOLATIONS TO LIST. YOU NEED A QUALIFIED ELECTRICIAN TO GET THIS UNIT IN ORDER
2) OVER SIZED OVER CURRENT PROTECTION UNDER SIZED WIRE
3) NOT COMPLING WITH THE UNIT LABEL
4) 120 VOLT SERVICE RECEPTACLE WIRED IN CORRECTLY
5) IDENTIFY ALL WIRES BY COLOR CODE
03/28/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SECURE THE ELEC. DISCONNECT ON ROOF
- SECURE ELEC. CONDUITS & TIGHTEN ALL LOOSE FITTINGS
- PROVIDE A GFI SERVICE RECEPTACLE & REWIRE
- MARK UNIT DATA PLATE W/PROPER HEAT STRIP AND FUSE ACCORDINGLY
- IDENTIFY FUSE BANKS IN DISCONNECT
- SECURE THE COVER PLATE IN DISCONNECT
- AC UNIT IS OVERFUSED
- CIRCUIT BREAKER NOT ADEQUATE FOR AC & HEAT STRIP
- BE SURE WIRE SIZE IS ADEQUATE
03/21/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE SCHEDULE AN INSPECTION
WHEN SOMEONE WILL BE HOME