Permit: T08ME00123

Parcel: 122122590


Addresses:

1619 N CATALINA AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/11/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/02/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- YOU CANNOT USE WHITE WIRE TO POWER THE AC UNIT
- TAPE BOTH ENDS OF WHITE WIRE WITH BLACK TAPE
- SERVICE RECEPTACLE CANNOT BE POWERED OFF THE AC DISCONNECT & YOU MUST HAVE A NEUTRAL WIRE NOT CONNECTED TO GROUND.
- NEED TO SEE NEW GAS PIPE & FITTINGS USED INSIDE HOUSE
03/14/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROPERLY IDENTIFY THE WHITE CONDUCTOR USED FOR HOT IN ELEC. DISCONNECT AND AT CIRCUIT BREAKER
- PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF
- CONDENSATE CANNOT TERMINATE ONTO A PATIO OR SIDEWALK
- SUPPORT PVC & PAINT W/LATEX PAINT
- 1/2" GAS PIPE NOT ADEQUATE FOR 92,000 BTU FURNACE MORE THAN 30' FROM THE METER
- PROVIDE MIN. 3/4" PIPE
- NEED TO SEE CIRCUIT BREAKER FOR AC UNIT