Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/02/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - YOU CANNOT USE WHITE WIRE TO POWER THE AC UNIT - TAPE BOTH ENDS OF WHITE WIRE WITH BLACK TAPE - SERVICE RECEPTACLE CANNOT BE POWERED OFF THE AC DISCONNECT & YOU MUST HAVE A NEUTRAL WIRE NOT CONNECTED TO GROUND. - NEED TO SEE NEW GAS PIPE & FITTINGS USED INSIDE HOUSE |
|
| 03/14/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROPERLY IDENTIFY THE WHITE CONDUCTOR USED FOR HOT IN ELEC. DISCONNECT AND AT CIRCUIT BREAKER - PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF - CONDENSATE CANNOT TERMINATE ONTO A PATIO OR SIDEWALK - SUPPORT PVC & PAINT W/LATEX PAINT - 1/2" GAS PIPE NOT ADEQUATE FOR 92,000 BTU FURNACE MORE THAN 30' FROM THE METER - PROVIDE MIN. 3/4" PIPE - NEED TO SEE CIRCUIT BREAKER FOR AC UNIT |