Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE THE REQUIRED DRAWING APPROVED BY THE CITY OF TUCSON FOR NEW A/C EQUIPMENT INSTALLED ON A ROOF TOP - THE DRAWING THAT WAS SUBMITTED & APPROVED SHOWS NO STRUCTURAL INTEGRITY - CONDENSATE WATER CANNOT DRIP ONTO THE GAS METERS - EXTEND DOWN SPOUT TO THE GROUND - 3/4" GAS PIPE WAS REQUIRED TO 76,000 BTU FURANCE 100' FROM METER |