Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08ME00093
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE |
|
03/03/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - 35 AMP FUSES NOT ADEQUATE - 1/2" PIPE TO FURNACE NOT ADEQUATE FOR 100,000 BTU - PROVIDE MIN. 3/4" 3/8" I.D X 2' GAS FLEX NOT ADEQUATE - PROVIDE 1/2" I.D GAS SHUT OFF VALVE AT FURNACE MUST PRECEDE THE GAS FLEX - USE 2 HOLE STRAPS TO SECURE GAS PIPE ON ROOF - CONDENSATE CANNOT TERMINATE ONTO THE SIDEWALK - PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF WITH A BUBBLE TYPE COVER - PROVIDE A PERMIT FOR THE ELEC. SERVICE UPGRADE - PAY A DOUBLE FEE FOR WORKING WITHOUT A PERMIT |