Inspection History: MECHANICAL - FINAL

Permit Number - T08ME00093

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/11/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
ALL CORRECTIONS HAVE BEEN MADE
03/03/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 35 AMP FUSES NOT ADEQUATE
- 1/2" PIPE TO FURNACE NOT ADEQUATE FOR 100,000 BTU
- PROVIDE MIN. 3/4" 3/8" I.D X 2' GAS FLEX NOT ADEQUATE
- PROVIDE 1/2" I.D GAS SHUT OFF VALVE AT FURNACE MUST PRECEDE THE GAS FLEX
- USE 2 HOLE STRAPS TO SECURE GAS PIPE ON ROOF
- CONDENSATE CANNOT TERMINATE ONTO THE SIDEWALK
- PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF WITH A BUBBLE TYPE COVER
- PROVIDE A PERMIT FOR THE ELEC. SERVICE UPGRADE
- PAY A DOUBLE FEE FOR WORKING WITHOUT A PERMIT