Permit: T08ME00093

Parcel: 133324620


Addresses:

9210 E SIMON PL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
03/11/2008 PLUMBING - GAS PRESS TEST FNL Approved
03/03/2008 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 1/2" GAS PIPE TO FURNACE 100' FROM METER NOT ADEQUATE FOR 100,000 BTU
- PROVIDE MIN. 3/4"
- 3/8" I.D X 2' GAS FLEX NOT ADEQUATE FOR 100,000 BTU
- PROVIDE MIN. 1/2" I.D
- GAS SHUT OFF VALVE FOR FURNACE MUST PRECEDE THE GAS FLEX CONNECTOR
- USE 2 HOLE STRAPS TO SECURE GAS PIPE ON ROOF