Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T08ME00093
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2008 | PLUMBING - GAS PRESS TEST FNL | Approved | ||
03/03/2008 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - 1/2" GAS PIPE TO FURNACE 100' FROM METER NOT ADEQUATE FOR 100,000 BTU - PROVIDE MIN. 3/4" - 3/8" I.D X 2' GAS FLEX NOT ADEQUATE FOR 100,000 BTU - PROVIDE MIN. 1/2" I.D - GAS SHUT OFF VALVE FOR FURNACE MUST PRECEDE THE GAS FLEX CONNECTOR - USE 2 HOLE STRAPS TO SECURE GAS PIPE ON ROOF |