Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/20/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio NO ACCESS TO ROOF |
|
| 03/12/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDENSATE MUST TERMINATE NOT MORE THAN 6" FROM GROUND LEVEL 2. IDENTIFY FUSE SIZE ON DATA PLATE REFER TO MANUFACTURES INSTRUCTIONS ON HOW TO DO THIS OR CALL 909-4878 REFEE ON NEXT INSPECTION IF NOT COMPLETE |
|
| 03/04/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL ALL EXTERIOR JOINTS AND SEAMS IN DUCT WORK 2. ALL PVC PIPE JOINTS MUST HAVE PRIMER 3. CONDENSATE PIPING CANNOT TERMINATE IN WASTE VENTS 4. PROPER VOLTAGE/AMPERAGE MUST BE IDENTIFIED ON UNIT DATA PLATE |