Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 02/26/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SECONDARY DRAIN CANNOT BE TIED INTO SAME PIPING AS PRIMARY DRAIN. - ALL PVC PIPING MUST HAVE PRIMER ON JOINTS. |
|
| 02/21/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON COIL. - PVC DRAIN IS TOO CLOSE TO FURNACE VENT CONNECTOR - USE COPPER TO GET PLASTIC 6" FROM VENT - PROVIDE A HIGH COMBUSTION AIR VENT - OK TO USE THE ONE OPENING METHOD - RECALL FOR INSPECTION |