Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 02/28/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDENSATE CANNOT BE TERMINATED ONTO THE PATIO - MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY - ID FUSE BANKS - SUPPORT THE ELEC. DISCONNECT - YOU CANNOT PULL POWER TO THE SERVICE RECEPTACLE FROM THE AC CIRCUIT - PROVIDE A NEUTRAL CONDUCTOR FROM THE ELEC. PANEL - USE A BUSHING INSIDE DISCONNECT TO SERVICE RECEPTACLE BOX. - USE A GREEN CONDUCTOR FOR GROUND TO RECEPTACLE - AC UNIT OVERFUSED |