Permit: T08ME00072

Parcel: 134120060

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/26/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
02/13/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
RELOCATE OVERFLOW SENSOR TO 6" AWAY FROM VENT CONNECTOR. USE COPPER.
PROVIDE A NEUTRAL WIRE UP TO ROOF FOR SERVICE RECEPTACLE. PROPERLY ID CONDUCTOR USED TO POWER DISCONNECT. TIGHTEN LOOSE ELEC. FITTINGS.
USE 15 OR 20 AMP FUSE FOR GFI
02/11/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REFRIGERATION LINES BLOCKING REMOVAL OF WATER HEATER AND NEED 6" CLEARANCE FROM FURNACE VENT CONNECTOR. PLASTIC DRAIN LINE NEEDS 6" CLEARANCE.
PROVIDE OVERFLOW SENSOR ON SECONDARY DRAIN
PROVIDE ACCESS TO ROOF
TIGHTEN ROMEX CONNECTOR ONTO FURNACE POWER CORD