Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 02/13/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* RELOCATE OVERFLOW SENSOR TO 6" AWAY FROM VENT CONNECTOR. USE COPPER. PROVIDE A NEUTRAL WIRE UP TO ROOF FOR SERVICE RECEPTACLE. PROPERLY ID CONDUCTOR USED TO POWER DISCONNECT. TIGHTEN LOOSE ELEC. FITTINGS. USE 15 OR 20 AMP FUSE FOR GFI |
|
| 02/11/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REFRIGERATION LINES BLOCKING REMOVAL OF WATER HEATER AND NEED 6" CLEARANCE FROM FURNACE VENT CONNECTOR. PLASTIC DRAIN LINE NEEDS 6" CLEARANCE. PROVIDE OVERFLOW SENSOR ON SECONDARY DRAIN PROVIDE ACCESS TO ROOF TIGHTEN ROMEX CONNECTOR ONTO FURNACE POWER CORD |