Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/20/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE AN OVERFLOW SENSOR IN SECONDARY DRAIN OUTLET ON COIL - PROVIDE THE ROMEX CONNECTOR ON FURNACE POWER CORD - CONNECT VENT PIPE TO WATER HEATER, INSTALL VENT RIGHT SIDE UP AND SCREW CONNECTIONS - PROVIDE AN APPROVED BUSHING IN ELEC. DISCONNECT - SUPPORT COPPER CONDENSATE DRAIN EVERY 6' - TERMINATE TO THE GROUND - PROVIDE AN APPROVED VENT CAP ON FURNACE VENT - PROVIDE MIN. 2" DUCT LINER IN DUCT ON ROOF |
|
| 02/28/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE A TRAP ON PRIMARY DRAIN - PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN - DO NOT HAVE PVC WITHIN 6" OF FURNACE VENT CONNECTOR - FINISH CONNECTION TO CONDENSATE PUMP - REMOVE TAPE FROM FURNACE & WATER HEATER VENT CONNECTORS - CANNOT CHECK FITTINGS - PROVIDE A ROMEX CONNECTOR ON FURNACE CORD - PROVIDE A BUSHING IN ELEC. DISCONNECT - CONDENSATE CANNOT TERMINATE INTO A SEWER VENT - PROVIDE ROOF JACKS AT ELEC. CONDUITS THRU THE ROOF - PROVIDE MIN. R-8 2" DUCT LINER IN ALL EXPOSED DUCT ON THE ROOF - PROVIDE AN APPROVED VENT CAP ON FURNACE VENT - PROVIDE DRAWINGS FOR STRUCTURAL LOAD APPROVED BY THE CITY OF TUCSON - LABEL THE CIRCUIT BREAKER FOR THE AC UNIT |
|
| 02/08/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT READY |