Permit: T08ME00058

Parcel: 134041170

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/11/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HERE. LEAVE HOMEOWNERS PHONE NUMBER WHEN SCHEDULING ALL INSPECTIONS.
02/01/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP
- FUSE STAT NOT REQUIRED
- TIGHTEN ROMEX CONNECTOR ONTO POWER CORD
- PROVIDE A SEDIMENT TRAP IN GAS LINE TO FURNACE AND WATER HEATER
- PROVIDE BOND FROM ELEC. SERVICE TO GAS PIPING
- PROVIDE THE REQUIRED DRAWING APPROVED BY THE CITY OF TUCSON FOR NEW INSTALL OF ROOFTOOP EQUIPMENT
- SUPPORT CONDENSATE DRAIN LINE EVERY 6'
- EXTEND WATER & HEATER VENTS MIN. 3' ABOVE COMBUSTION AIR VENTS. USE DOUBLE WALL PIPE.
- PROVIDE A GROUND WIRE FOR THE SERVICE RECEPTACLE AND USE PROPER COLOR WIRE FOR THE HOT.