Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08ME00057
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/11/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - OK TO OPERATE HEATING SYSTEM - PROVIDE R.4.2 INSULATION ON EXTERIOR OF DUCT WORK ON ROOF |
|
01/31/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO P-TRAP ON CONDENSATE FLEX CANNOT ENTER CABINET CONDENSATE NOT PROPERLY ROUTED ROOFTOP DUCT TO HAVE R-8 INSULATION NO SEDIMENT TRAP ON GAS LINES THIS IS A NEW INSTALL, PROVIDE PROPER DESCRIPTION OF WORK ALSO, PROVIDE LOAD CALCULATIONS FOR ROOF 1810 AND 1812 |