Permit: T08ME00017

Parcel: 133141700


Addresses:

1660 N PASEO DORADO

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/14/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
01/30/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SECURE THE GAS LINE TO THE BLOCKS ON THE ROOF
- TIGHTEN THE LOOSE ELEC. CONNECTION TO THE AC UNIT
- DISCONNECT IS OVERFUSED
- COVER PLATE INSIDE DISCONNECT WON'T STAY IN
- BLOCK & CLAMP CONDENSATE DRAIN EVERY 4' & SECURE TO BLOCKS
- PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON THE ROOF WITH A WATERPROOF BUBBLE TYPE COVER
- RECALL FOR INSPECTION