Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/24/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE ALL FOIL TAPE FROM VENT CONNECTORS. |
|
| 12/14/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSULATE SHEET METAL SLEEVES ON FURNACES. REMOVE ALL FOIL TAPE FROM FURNACE VENTS & PROVIDE MINIMUM OF 3 SCREWS IN EACH JOINT OF VENT CONNECTOR. REMOVE ANY PVC FROM WITHIN 6" OF VENT & REPLACE WITH COPPER. |