Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04820
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2009 | INSP - FULL | Approved | ||
01/02/2009 | INSP - FULL | Correction Required | ACCORDING TO THE ANNUAL SPRINKLER REPORT DATED SEPTEMBER, 06,2007 ( THE SYSTEM IS NOW DUE FOR AN OTHER ANNUAL) THE SPRINKLERS INSTALLED ARE OVER 50 YEARS OLD. N. F. P. A. #25-INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS, SECTION 5.3.1.1.1, STATES THAT "WHERE SPRINKLERS HAVE BEEN IN SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS SHALL BE TESTED. TEST PROCEEDURES SHALL BE REPEATED AT 10 YEAR INTERVALS. THIS DEFICIENCY SHALL BE COMPLETED WITH IN 90 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE. | |
12/29/2008 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS " SPRINKLERS " ARE REQUIRED TO BE TESTED AND INSPECTED ON AN ANNUAL BASIS. THE LAST REPORT OF RECORD THAT THE FIRE PREVENTION OFFICE HAS RECEIVED IS DATED 2002. IF THE SYSTEM HAS BEEN INSPECTED WITHIN THE LAST YEAR, PLEASE FORWARD A COPY OF THAT REPORT WITH IN 30 DAYS TO THIS OFFICE |