Case: T08FR04756

Parcel: 137053090


Addresses:

5242 S 12TH AV


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR04756

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
12/18/2008 VIOL - MEANS OF EGRESS Violation TFC 504.2 - Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval.
12/18/2008 VIOL - MEANS OF EGRESS Violation TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
_____ Clear exit path, and maintain it this way.
12/18/2008 VIOL - MEANS OF EGRESS Violation TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
_____ Provide emergency lighting that is activated by loss of power to building.
12/18/2008 VIOL - MEANS OF EGRESS Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.
_____ Repair/replace exit signs