Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR04720

Parcel: 13706018C


Addresses:

5339 S 12TH AV


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR04720

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
12/12/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
_____ Replace with approved power strip.
_____ Remove extension cord and/or replace with approved permanent electrical power source.
12/12/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.