Case: T08FR04679

Parcel: 13409013B


Addresses:

550 S CAMINO SECO


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T08FR04679

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
12/09/2008 INSP - FULL Violation Problem: Fire Doors near 1310 ( not closing), 1207 ( not closing) Bld #1 on 2nd floor (not working), B#2 near P216 ( no doorsweep), Bld#2, 2nd Floor, middle fire door ( not working), Bld # 3, 1st floor, middle door ( missing doorswee) Bld#3, 2nd floor, middle door( missing doorsweep), Bld # 3, 3rd floor, middle door ( not working ) Bld #4, 3rd Floor exit door ( not closing), Bld #4, 2nd floor, middle door, (not closing). Where ever a required fire door does not close fully or swing closed fully on its own, itshall be repaired or replaced. Where ever a door sweep is missing from a fire door rated assembly, it shall be replaced.
IFC 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: FIRE DOORS SHALL OPERATE PROPERLY.
12/09/2008 INSP - FULL Violation Problem: Emergency Lights do not function properly. Near unit #1101 and, Building #2 near #P212, near #2107, near P223,
IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
REQUIRED CORRECTION: EMERGENCY LIGHTING UNITS SHALL BE FUNCTIONING PROPERLY.
12/09/2008 INSP - FULL Violation Problem: Open sockets near #1310, #1316, Building #4 in 3rd floor hallway, 1st floor near #4105.
IFC 605.6 Unapproved conditions. Open junction boxes and open-siring splices shall be prohibited. Approved covers shall e provided for all switch and electrical outlet boxes.
REQUIRED CORRECTION: ALL OUTLETS SHALL HAVE FACE PLATES OR PROPER COVERS.
12/09/2008 INSP - FULL Violation Exit signs not fully lit in Bld#2 near P212, Bld #3 3rd floor, Bld#4 1st floor ( cover over sign missing)
IFC 1011.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be intalled in accordance with the manufacturer's instructions and Section 2702 of the IBC. Exit signs shall be illuminated at all times.
REQUIRED CORRECTION: REPLACE MISSING/BURNT BULBS. REPLACE BACK UP BATTERIES AS NECESSARY, REPLACE PLASTIC CLEAR COVER OVER EXIT SIGN.