Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2008 | INSP - FULL | Approved | ALL NOTEDTFC VIOLATIONS HAVE BEEN CORRECTED. | |
| 12/08/2008 | INSP - FULL | Violation | 1.) TFC 1011.4 REPAIR NUMEROUS EXIT SIGNS THROUGHOUT THE FACILITY SO THAT THEY ARE ILLUMINATED. | |
| 12/08/2008 | INSP - FULL | Violation | 2.) TFC 901.6 SPRINKLER HEAD ESCUTCHEON MISSING IN STORAGE ROOM NEAR ROOM # 203. | |
| 12/08/2008 | INSP - FULL | Violation | 3.) TFC 1027.5 REPAIR EMERGENCY ILLUMINATION UNIT NEAR ROOM # 304. | |
| 12/08/2008 | INSP - FULL | Violation | 4.) TFC 605.3 PROVIDE A 30" WORKING SPACE IN FRONT OF ELECTRICAL PANELS IN MECHANICAL ROOM NEAR LIFE ENRICHMENT OFFICE. | |
| 12/08/2008 | INSP - FULL | Violation | 5.) TFC 1027.5 REPAIR EMERGENCY ILLUMINATION UNIT BY ROOM # 501. | |
| 12/08/2008 | INSP - FULL | Violation | 6.) TFC 1027.5 REPAIR EMERGENCY ILLUMINATION UNIT BY ROOM # 805. | |
| 12/08/2008 | INSP - FULL | Violation | 7.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN HALLWAY OUTSIDE OF KITCHEN. | |
| 12/08/2008 | INSP - FULL | Violation | 8.) TFC 510.1 PLACE AN APPROVED SIGN ON DOOR FOR SPRINKLER SYSTEM RISER STATING "RISER ROOM". | |
| 12/08/2008 | INSP - FULL | Violation | NOTE: FIRE DRILL RECORDS ARE CURRENTLY IN COMPLIANCE. FIRE ALARM, SPRINKLER SYSTEM AND KITCHEN TYPE 1 HOOD INSPECTION REPORTS ARE CURRENT AND WERE MADE AVAILABLE UPON INSPECTION. |