Case: T08FR04638

Parcel: 12101005A


Addresses:

6161 E PIMA ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/14/2009 INSP - FULL Approved PRE-CITATION DELEATED, SPKLR. REPORT TO SYSTEMS
04/10/2009 INSP - FULL Correction Required PRECITATION SENT 4-9-09
02/04/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 12-9-2008 FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 6161 E. PIMA. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT
12/09/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE

1) THE PAINTED SPRINKLER HEADS, 3 EA.IN THE GYM AND I EA. IN THE LAUNDRY ROOM SHALL BE CHANGED OUT
12/05/2008 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS