Case: T08FR04565

Parcel: 12616319B


Addresses:

445 S ALVERNON WY

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/24/2009 INSP - FULL Approved
12/04/2008 INSP - FULL Violation 1). Fire sprinkler and test report shall be submitted to TFD. And required repairs shall be completed at by abatement date. IFC 901.6
2). Fire alarm test report shall be submitted to TFD and repairs shall be completed by abatement date. IFC 901.6
3). Mount or remove portable fire extinguisher in sales office. IFC 901.6
4). Repair holes in banquet storage room. IFC 703.1
5). Exit light out of service in Bonsai Room. IFC 1027.3
6). Currently the breakfast kitchen is not service. The hood system must be maintained. To remove contact Deputy Chief Dan Uthe for removal.
IFC 901.6
7). Currently class k extinguishers in breakfast bar are not mounted. These shall be mounted. IFC 901.6
8). Currently in main kitchen, class K extinguishers are not mounted within 30 feet from cooking operation. IFC 904.11.5
9). Remove extension cord between ceiling in Javelina Cantina. IFC 605.1
10). Expired extinguishers are in the following areas: Javelina Cantina, admin offices, in main kitchen. IFC 901.6
11). Kitchen hoods system is due for cleaning. Due Nov. 08. IFC 904.11.6.3
12). Please replace pull station. The cover is coming off. IFC 901.6
13). Please place sign stating STANDPIPE on permanent portion of fence, identifying standpipe. IFC 905.2.