Case: T08FR04534

Parcel: 12601003C


Addresses:

4500 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/23/2008 INSP - FULL Approved *** NOTE
ITEM # 2 FROM THE WRITE UP IS BEING TRANSFERED TO A NEW REPORT FOR SUITE # 110 AT 4500 E. SPEEDWAY. THE
DESTINY CHURCH INTERNATIONAL.
12/02/2008 INSP - FULL Correction Required 8) MAMAS PIZZA - THE BOTTOM GUAGE SHALL BE SHANGED OUT FOR A CORRECT READING. A NEW PRESSURE READING SHALL BE PROVIDED THIS OFFICE
12/02/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE.

1) THE FIRE DEPARTMENT CONNECTION IS MISSING PROTECTIVE CAPS AND GASKETS, BOTH SHALL BE REPLACED

2) CHURCH - NO ITEMS SHALL BE HUNG FROM SPRINKLER PIPING. REMOVE SPEAKERS AND WIRING.

3) PROVIDE 2, 200 DEGREE 1/2 " STANDARD UPRIGHT SPRINKLERS AT THE HEAD BOX.

4) STARVING STUDENTS - PROVIDE SPRINKLER COVERAGE TO THE OFFICE

5) CHURCH - PROVIDE SPRINKLER COVERAGE TO THE CLOSET BY THE KITCHEN

6) VENTURES SUITE - PROVIDE SPRINKLER COVERAGE TO THE FRONT OFFICES

7) IF THE CONTROL VALVE IS NOT IN A SECURE AREA A LOCK AND CHAIN SHALL BE PROVIDED