Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2009 | INSP - FULL | Approved | COPY OF REPAIRS SENT TO SYSTEMS | |
| 12/02/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL FIRE SPRINKLER INSPECTION, 11-5-08, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE. 1) THE 3/4" X 5" NIPPLE AT THE ALARM VALVE THAT IS LEAKING AND RUSTED SHALL BE CHANGED OUT 2) THE SPARE HEAD BOX NEEDS A WRENCH TO FIT THE STAR-E AND STAR LD2 SPRINKLERS 3) THE SPARE HEAD BOX NEEDS 2 VERTICLE SIDEWALLS 4) AT THE EAST DANCE FLOOR THERE ARE 2 SPRINKLERS TO CLOSE TOGETHER. ONE MAY BE REMOVED OR A BAFFEL MAY BE USED 5) A SPRINKLER HEAD GUARD SHALL BE SUPPLIED AT THE ENTRY, DANCE FLOOR EAST, TO THE LADIES DRESSING ROOM, IF THE SPRINKLER IS LOWER THAN 6' 6) CHANGE OUT THE OLD STYLE SPRINKLER IN THE MANAGERS OFFICE TO COINCIDE WITH THE INSTALLED SPRINKLERS 7) THE DROP IN THE STORE ROOM NEXT TO THE STEPS NEEDS TO BE SEALED AT THE CEILING PENETRATION |