Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2009 | INSP - FULL | Approved | ELECTRIC BELL WORKING, BREAKER WAS TURNED OFF AS PER JESSIE, (404-0388) 0F LA PALOMA FAMILY SERVICES | |
| 03/20/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. THE CONTRACTOR OF RECORD SHALL FORWARD A COPY OF THE REPAIR MANIFEST. 1) REPLACE THE MISSING GASKETS AT THE FIRE DEPARTMENT CONNECTION. 2) PROVIDE A SPARE HEAD BOX WITH THE CORRECT COMPLIMENT OF SPARE HEADS AND A SPECIAL WRENCH. 3) THE ELECTRIC BELL IS NOT WORKING AND SHALL BE REPAIRED |
|
| 03/06/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-28-2008, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 240 W. NAVAJO. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 11/28/2008 | INSP - FULL | Correction Required | RE: 240 W. NAVAJO FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS. WHERE AS THE LAST REPORT OF INSPECTION RECEIVED BY THIS OFFICE IS DATED 2004, A CURRENT COPY SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE WITHIN 30 DAYS. |