Case: T08FR04454

Parcel: 13324012B


Addresses:

8110 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04454

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2009 INSP - FULL Approved Sprinkler annual inspection done, deficiencies done, 5 year valve inspection done. Per Captain Mike Jones, system is in compliance at this time.
04/20/2009 INSP - FULL Correction Required PRE-CITATION DELEATED, INSPECTION REPORT RECEIVED, WORKING ON DEFICIENCIES

DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIOFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE

1) THE SPRINKLER HEAD SPACING IN THE MANAGERS OFFICE SHALL BE CORRECTED

2) THE CORRODED CHECK VALVE AT THE SPRINKLER RISER SHALL BE CHANGED OUT

3) PROVIDE SIGNAGE FOR ALL CONTROL VALVES

4) THE WATER FLOW ALARM INDICATION AT THE FIRE ALARM PANEL SHALL BE IN REPAIR.
04/10/2009 INSP - FULL Correction Required PRECITATION SENT 4-9-09
02/05/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR FOR THE NOTICE DATED 11-26-08, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 8110 E. SPEEDWAY. IF CORRECTEDHAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
11/26/2008 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS