Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04454
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2009 | INSP - FULL | Approved | Sprinkler annual inspection done, deficiencies done, 5 year valve inspection done. Per Captain Mike Jones, system is in compliance at this time. | |
04/20/2009 | INSP - FULL | Correction Required | PRE-CITATION DELEATED, INSPECTION REPORT RECEIVED, WORKING ON DEFICIENCIES DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIOFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE 1) THE SPRINKLER HEAD SPACING IN THE MANAGERS OFFICE SHALL BE CORRECTED 2) THE CORRODED CHECK VALVE AT THE SPRINKLER RISER SHALL BE CHANGED OUT 3) PROVIDE SIGNAGE FOR ALL CONTROL VALVES 4) THE WATER FLOW ALARM INDICATION AT THE FIRE ALARM PANEL SHALL BE IN REPAIR. |
|
04/10/2009 | INSP - FULL | Correction Required | PRECITATION SENT 4-9-09 | |
02/05/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR FOR THE NOTICE DATED 11-26-08, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 8110 E. SPEEDWAY. IF CORRECTEDHAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
11/26/2008 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS |