Case: T08FR04441

Parcel: 13323090A


Addresses:

7890 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T08FR04441

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
12/24/2008 VIOL - MOTOR FUEL DISPENSING Approved Extinguishers are serviced
11/25/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill-pipe openings.

· The fire extinguishers shall be inspected annually.


2204.2 Attended self-service motor fuel-dispensing facilities.
Attended self-service motor fuel-dispensing facilities shall have at least one qualified attendant on duty while the facility is open for business. The attendant's primary function shall be to supervise, observe and control the dispensing of fuel. The attendant shall control sources of ignition, give immediate attention to accidental spills or releases, and be prepared to use fire extinguishers.
11/25/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times.

· Hoses on pumps 1,2,5 and 6 are cracked.