Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MOTOR FUEL DISPENSING
Case Number - T08FR04441
Inspection Description - VIOL - MOTOR FUEL DISPENSING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2008 | VIOL - MOTOR FUEL DISPENSING | Approved | Extinguishers are serviced | |
| 11/25/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill-pipe openings. · The fire extinguishers shall be inspected annually. 2204.2 Attended self-service motor fuel-dispensing facilities. Attended self-service motor fuel-dispensing facilities shall have at least one qualified attendant on duty while the facility is open for business. The attendant's primary function shall be to supervise, observe and control the dispensing of fuel. The attendant shall control sources of ignition, give immediate attention to accidental spills or releases, and be prepared to use fire extinguishers. |
|
| 11/25/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times. · Hoses on pumps 1,2,5 and 6 are cracked. |