Case: T08FR04438

Parcel: 134071880


Addresses:

8509 E KENYON DR

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
03/31/2009 VIOL - FIRE PROTECTION SYSTEMS Approved
11/25/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 907.3.1.8 Group R-4. A fire alarm system shall be
installed in existing Group R-4 residential care/assisted
living facilities.

Exceptions:
1. Where there are interconnected smoke alarms
meeting the requirements of Section 907.2.10
and there is at least one manual fire alarm box per
floor arranged to sound continuously the
smoke alarms.
2. Other manually activated, continuously sounding
alarms approved by the fire code official.

____Install a local fire alarm consisting of one pull station
and one audible device. Locate near the main/front exit.
11/25/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 903.2.7 Group R. Existing sorority and fraternity house and
existing Group R-4 occupancies shall have automatic sprinkler
systems installed. A permit shall be issued within two years of
the adoption of this code and the work shall be completed within
three years of the adoption of this code.

____This ordinance took effect on October 23, 2007 and requires
completion by October 22, 2010.