Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04431
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
11/25/2008 | INSP - FULL | Violation | 1.) TFC 1011.4 THE INTERNALLY ILLUMINATED EXIT SIGN ABOVE B UNIT WEST EXIT DOOR MUST BE ILLUMINATED AT ALL TIMES. | |
11/25/2008 | INSP - FULL | Violation | 2.) TFC 1011.4 THE INTERNALLY ILLUMINATED EXIT SIGN LOCATED ACROSS FROM SUPPLY ROOM MUST BE ILLUMINATED AT ALL TIMES. | |
11/25/2008 | INSP - FULL | Violation | 3.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ACROSS FROM SUPPLY ROOM IS NOT ILLUMINATING. | |
11/25/2008 | INSP - FULL | Violation | 4.) TFC 1008.1.8.4 THE SLIDE BOLT LOCK ON KENNY'S DOOR MUST BE REMOVED. | |
11/25/2008 | INSP - FULL | Violation | 5.) TFC 3003.5.3 THE COMPRESSED GAS CYLINDERS IN SHOP MUST BE SECURED TO PREVENT FALLING. | |
11/25/2008 | INSP - FULL | Violation | 6.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ON SOUTH WALL OF MECHANICAL ROOM IS NOT ILLUMINATING. | |
11/25/2008 | INSP - FULL | Approved | NOTE: AUTOMATIC SPRINKLER SYSTEM INSPECTION REPORT AND FIRE ALARM INSPECTION REPORT WAS PROVIDED AT TIME OF INSPECTION. FIRE DRILL RECORDS ARE IN COMPLIANCE. ALL RECORDS ARE KEPT IN EXCELLENT ORDER. |