Case: T08FR04392

Parcel: 12212010A


Addresses:

4629 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - NIGHT

Case Number - T08FR04392

Inspection Description - INSP - NIGHT

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2009 INSP - NIGHT Approved PRE-CITATION DELETED, ALL CORRECTIONS MADE, REVISED INSPECTION TO SYSTEMS
04/28/2009 INSP - NIGHT Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. THIS OFFICE REQUIRES A COPY OF THE REPAIR MANIFEST

1) REPLACE THE MISSING GASKETS AT THE FIRE DEPT. CONNECTION

2) REPLACE THE LEAKING SPRINKLER HEAD IN THE BREAK ROOM

3) REPLACE THE GUAGE WITH THE MISSING PROTECTIVE GLASS

4) PROVIDE A 5 YEAR INTERNAL VALVE INSPECTION

5) REPLACE THE INSULATION THAT IS IMPEDING SPRINKLER OPERATION

THE PRE-CITATION NOTICE WILL BE IN FORCE UNTIL REPAIRS ARE DONE
04/10/2009 INSP - NIGHT Correction Required PRECITATION SENT 4-9-09
02/04/2009 INSP - NIGHT Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-21-08, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 4629 E. SPEEDWAY. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
11/21/2008 INSP - NIGHT Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ANNUALLY