Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/04/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
1.) TFC 605.6 ELECTRICAL JUNCTION BOX ABOVE ENVIRONMENTAL SERVICES OFFICE MUST HAVE A COVER PLATE INSTALLED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
2.) TFC 1011.1 AN ILLUMINATED EXIT SIGN IS REQUIRED ABOVE DOOR # 050-06A. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
3.) TFC 703.1.1 BROKEN CEILING TILE ABOVE EXIT SIGN IN BASEMENT CORRIDER OUTSIDE OF CLEAN LINEN ROOM MUST BE REPLACED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
4.) TFC 315.2.3 COMBUSTIBLE STORAGE IN MECHANICAL ROOM B-10 MUST BE REMOVED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
5.) TFC 905.2 OUTLET VALVE FOR STANDPIPE CONNECTIONS OUTSIDE OF ROOF ACCESS DOOR ON EAST BUILDING IS STUCK IN CLOSED POSITION. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
6.) TFC 901.6 ON 5TH FLOOR IN DIALYSIS ROOM THE PRIVACY CURTAIN MUST HAVE 1/2" MESH NOT 1/4" MESH. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
7.) TFC 1011.4 0N 4TH FLOOR EAST END OF INTERSTITIAL THE EXIT SIGN ABOVE DOOR # 400-141A IS NOT ILLUMINATED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
8.) TFC 605.6 ON 3RD FLOOR IN ROOM #303-34B OUTLET COVER PLATE MUST BE INSTALLED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
9.) TFC 703.1.1 IN ROOM #303-34B CEILING TILE MUST BE IN PLACE. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
10.) TFC 1028.2 2ND FLOOR CORRIDORS MUST HAVE TRASH CANS WITHOUT WHEELS REMOVED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
11.) TFC 703.1.1 IN RADIOLOGY HOUSEKEEPING CLOSET # 100-05A NEX TO MEN'S ROOM CEILING TILE ARE MISSING. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
12.) TFC 703.1.1 ON 1ST FLOOR ELECTRICAL ROOM # 160-19 BY AMBULATORY SURGERY ELEVATOR HAS CEILING PENETRATIONS AND OPENING AROUND CONDUIT MUST BE SEALED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
13.) TFC 605.5 IN OUTPATIENT ADMITTING THE EXTENSION CORD POWERING THE COPY MACHING OUTSIDE OF CUBICLE IS NOT ALLOWED TO BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
14.) TFC 1011.4 IN O'REILLY CENTER THE WEST EXIT SIGN IS NOT ILLUMINATED. |
| 11/20/2008 |
INSP - FULL |
|
Violation |
15.) TFC 703.1.1 IN NEW BUILDING 1ST FLOOR ELECTRICAL CLOSET NEAR PHYSICAL THERAPY, ELECTRICAL CONDUIT NOT SEALED. |