Case: T08FR04387

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/04/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
11/20/2008 INSP - FULL Violation 1.) TFC 605.6 ELECTRICAL JUNCTION BOX ABOVE ENVIRONMENTAL SERVICES OFFICE MUST HAVE A COVER PLATE INSTALLED.
11/20/2008 INSP - FULL Violation 2.) TFC 1011.1 AN ILLUMINATED EXIT SIGN IS REQUIRED ABOVE DOOR # 050-06A.
11/20/2008 INSP - FULL Violation 3.) TFC 703.1.1 BROKEN CEILING TILE ABOVE EXIT SIGN IN BASEMENT CORRIDER OUTSIDE OF CLEAN LINEN ROOM MUST BE REPLACED.
11/20/2008 INSP - FULL Violation 4.) TFC 315.2.3 COMBUSTIBLE STORAGE IN MECHANICAL ROOM B-10 MUST BE REMOVED.
11/20/2008 INSP - FULL Violation 5.) TFC 905.2 OUTLET VALVE FOR STANDPIPE CONNECTIONS OUTSIDE OF ROOF ACCESS DOOR ON EAST BUILDING IS STUCK IN CLOSED POSITION.
11/20/2008 INSP - FULL Violation 6.) TFC 901.6 ON 5TH FLOOR IN DIALYSIS ROOM THE PRIVACY CURTAIN MUST HAVE 1/2" MESH NOT 1/4" MESH.
11/20/2008 INSP - FULL Violation 7.) TFC 1011.4 0N 4TH FLOOR EAST END OF INTERSTITIAL THE EXIT SIGN ABOVE DOOR # 400-141A IS NOT ILLUMINATED.
11/20/2008 INSP - FULL Violation 8.) TFC 605.6 ON 3RD FLOOR IN ROOM #303-34B OUTLET COVER PLATE MUST BE INSTALLED.
11/20/2008 INSP - FULL Violation 9.) TFC 703.1.1 IN ROOM #303-34B CEILING TILE MUST BE IN PLACE.
11/20/2008 INSP - FULL Violation 10.) TFC 1028.2 2ND FLOOR CORRIDORS MUST HAVE TRASH CANS WITHOUT WHEELS REMOVED.
11/20/2008 INSP - FULL Violation 11.) TFC 703.1.1 IN RADIOLOGY HOUSEKEEPING CLOSET # 100-05A NEX TO MEN'S ROOM CEILING TILE ARE MISSING.
11/20/2008 INSP - FULL Violation 12.) TFC 703.1.1 ON 1ST FLOOR ELECTRICAL ROOM # 160-19 BY AMBULATORY SURGERY ELEVATOR HAS CEILING PENETRATIONS AND OPENING AROUND CONDUIT MUST BE SEALED.
11/20/2008 INSP - FULL Violation 13.) TFC 605.5 IN OUTPATIENT ADMITTING THE EXTENSION CORD POWERING THE COPY MACHING OUTSIDE OF CUBICLE IS NOT ALLOWED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
11/20/2008 INSP - FULL Violation 14.) TFC 1011.4 IN O'REILLY CENTER THE WEST EXIT SIGN IS NOT ILLUMINATED.
11/20/2008 INSP - FULL Violation 15.) TFC 703.1.1 IN NEW BUILDING 1ST FLOOR ELECTRICAL CLOSET NEAR PHYSICAL THERAPY, ELECTRICAL CONDUIT NOT SEALED.