Case: T08FR04380

Parcel: 11446206B

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04380

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2008 INSP - FULL Approved
11/20/2008 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE

1) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION

2) THE SPARE HEAD BOS NEEDS A SPECIAL WRENCH FOR CHANGING SPRINKLER HEADS

3) IF THE MAIN CONTROL VALVE IS NOT IN A SECURE AREA, THE CONTROL VALVE SHALL BE SECURED WITH A LOCK AND CHAIN

4) THE SUPPLY GUAGE WAS DAMAGED, IT SHALL BE REPLACED AND A FLOW TEST PERFORMED FOR REQUIRED PRESSURE READINGS.

5) A 3 FOOT CLEARANCE SHALL BE PROVIDED AT THE SPRINKLER RISER FOR ACCESSABILITY