Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2008 | INSP - FULL | Approved | ||
| 11/18/2008 | INSP - FULL | Violation | 1). Fire sprinkler test and inspection shall be submitted. IFC 901.6 2). Fire alarm test shall be submitted. IFC 901.6 3). Fire pump test report shall be submitted. IFC 901.6 4). Candles shall used in building unless approved. IFC 308.3.2 5). Currently there are holes in walls and ceilings in the following areas. 6th floor electrical room, 2nd floor mech room.. IFCC 703.1 These shall be repaired. 6). Fire drill is required. Date shall be determined by 12-10-08 |