Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
| 11/17/2008 | INSP - FULL | Violation | 1.) TFC 315.2.1 IN NEW CAR FILE ROOM STORAGE MUST BE MAINTAINED 18" BELOW SPRINKLER HEAD DEFLECTOR. | |
| 11/17/2008 | INSP - FULL | Violation | 2.) TFC 901.6 SPRINKLER HEAD ESCUTCHEON ABOVE DOOR FOR FRONT PARTS COUNTER MUST BE IN PLACE. | |
| 11/17/2008 | INSP - FULL | Violation | 3.) TFC 605.5 EXTENSION CORD POWERING OIL RECOVERY PUMP IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. | |
| 11/17/2008 | INSP - FULL | Violation | 4.) TFC 605.4 THE MULTI-PLUG ADAPTER AT WORK BAY #4 IS NOT PERMITTED BY THE FIRE CODE. |
|
| 11/17/2008 | INSP - FULL | Violation | 5.) TFC 605.4 THE CUBE TYPE ELECTRICAL PLUG ADAPTER AT WORK BAY # 12 IN NOT PERMITTED BY THE CODE. | |
| 11/17/2008 | INSP - FULL | Violation | 6.) TFC 315.2.1 IN TIRE ROOM STORAGE MUST BE MAINTAINED 18" BELOW SPRINKLER HEAD DEFLECTOR. | |
| 11/17/2008 | INSP - FULL | Violation | 7.) TFC 605.4.2 IN SERVICE ADVISOR ROOM # 1 THE POWER STRIP MUST BE PLUGGED DIRECTLY INTO AN OUTLET AND NOT POWERED BY AN EXTENSION CORD. |