Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04286
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2009 | INSP - FULL | Approved | A BUSINESS INSPECTION WAS CONDUCTED BY INSP. BIEG ON 3/27/09. ALL DEFICIENCIES WERE CORRECTED AT THAT TIME | |
| 02/03/2009 | INSP - FULL | Approved | DURING THE SPRINKLER INSPECTION DATED 1-9-09 THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORECTED WITH IN 30 DAYS. 1) ALL STOCK IN THE SHOE DEPT. SHALL BE LOWERED TO NO CLOSER THAN 18 INCHES BELOW SPRINKLER HEADS. PLEASE NOTIFY THIS INSPECTOR WHEN DONE SO THAT AN ON SITE INSPECTION CAN BE ACCOMPLISHED. |
|
| 02/03/2009 | INSP - FULL | Correction Required | ||
| 11/10/2008 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS, SPRINKLER AND ALARMS, ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS. THE LAST REPORT ON RECORD AT THIS OFFICE IS FROM 2004. THE SYSTEM SHALL BE TESTED WITHIN 30 DAYS AND A COPY OF THE INSPECTION FORWARDED TO THIS OFFICE. IF TESTING HAS BEEN DONE WITHIN THE LAST, A COPY OF THAT REPORT CAN BE SENT. |