Case: T08FR04285

Parcel: 10511061A


Addresses:

4570 N ORACLE RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04285

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2009 INSP - FULL Approved PRE-CITATION DELEATED, REPORT OF CORRECTION RECEIVED
04/10/2009 INSP - FULL Correction Required PRECITATION SENT 4-8-09
11/21/2008 INSP - FULL Correction Required DURING THE ANNUAL FIRE PROTECTION SYSTEMS INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED.

SPRINKLER SYSTEM
1) PROVIDE A HYDRAULIC CALCULATION PLATE AT THE SPRINKLER RISER

FIRE ALARM SYSTEM
1) AN ELEVATOR RECALL KEY SHALL BE PROVIDED SO THAT THE SMOKE DETECTOR FOR RECALL MAY BE TESTED.
11/10/2008 INSP - FULL Correction Required 1) FIRE PROTECTION SYSTEMS, SPRINKLER AND ALARMS, ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS. THE LAST REPORT ON RECORD AT THIS OFFICE IS FROM 2004. THE SYSTEM SHALL BE TESTED WITH IN 30 DAYS AND A COPY OF THE INSPECTION SHALL BE FORWARDED TO THIS OFFICE. IF TESTING HAS BEEN COMPLETED WITHIN THE LAST YEAR, A COPY OF THAT REPORT CAN BE SENT.