Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2009 | INSP - FULL | Approved | CONTRACTORS REVISED REPORT TO SYSTEMS | |
| 12/12/2008 | INSP - FULL | Approved | ||
| 12/12/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION, 10-28-2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWADED TO THE FIRE PREVENTION OFFICE. 1) PROVIDE A CAP FOR THE FIRE DEPARTMENT CONNECTION 2) PRIVIDE 2, HORIZONTAL QUICK RESPONSE SIDEWALL SPRINKLER HEADS FOR THE HEAD BOX 3) PROVIDE SIGNAGE FOR THE MAIN DRAIN 4) CHANGE OUT THE CORRODED DRY PENDANT SPRINKLER HEAD IN THE COOLER 5) IN THE COOKING AREA - AND DISH WASH LINE, SPRINKLER HEADS THAT ARE GREASE LADEN SHALL BE CHANGED OUT. AFTER CHANGING THEY MAY BE COVERED WITH A SMALL BAGGIE TO KEEP THEM CLEAN 6) THE SPRINKLER HEADS THAT ARE DUST LOADEN MAY BE CLEANED WITH A SOFT BRUSH. NO HARSH CHEMICLES CAN BE USED 7) IF THE CONTROL VALVE IS NOT IN A SECURE AREA IT SHALL BE SECURED WITH A LOCK AND CHAIN TO PREVENT TAMPERING 6) |
|
| 11/10/2008 | INSP - FULL | Correction Required | 1) FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ANNUALY. THE LAST REPORT OF INSTECTION THAT THIS OFFICE HAS RECEIVED IS DATED APRIL, 03, 2006. IF A CURRENT REPORT IS AVAILABLE, WITH IN THE LAST YEAR, PLEASE FORWARD TO THIS OFFICE. IF NOT IT IS REQUIRED TO BE DONE WITH IN 30 DAYS |