Date Description Inspector Results Comments
12/19/2008 INSP - FULL Approved FIELD INSP. DONE BY INSP. SCHULTZ
11/10/2008 INSP - FULL Correction Required DURING THE LAST ANNUAL FIRE SPRINKLER INSPECTION THAT THIS OFFICE HAS ON FILE (4-24-2007) THE FOLLOWING DEFICIENCY WAS FOUND. IF CORRECTIONS HAVE BEEN MADE PLEASE FORWARD A COPY . IF DEFICIENCIES ARE STILL OUTSTANDING REPAIRS SHALL BE MADE WITH IN 30 DAYS AND A COPY OF THAT MANIFEST FORWARDED.

1) PROVIDE THE CORRECT WRENCH AT THE SPARE HEAD CABINET FOR THE SPRINKLERS

2) IN THE FOLLOWING AREAS SPRINKLERS ARE CLOSER TOGEATHER THAN THE ALLOWABLE DISTANCE, A BAFFEL CAN BE INSTALLED OR A HEAD SHALL BE PLUGGED OUT, IN THE LAND ROOM AND SECOND FLOOW WEST BY 2W179

3) IN THE HALL OUTSIDE OF THE INTERVIEW ROOMS A SPRINKLER EXCEEDS THE ALLOWABLE DISTANCE OFF A WALL

4) UNDER THE STAIRS AT THE STOREROOMNEXT TO ROOM 101, A HEAD GUARD IS NEEDED TO PROTECT THE SPRINKLER HEAD FROM PHYSICAL DAMAGE

5) THE INSPECTING CONTRACTOR STATED THAT AT THE SECOND FLOOR CENTER ( NORTH OF THE LADIES ROOM ) AND AT THE AREA WEST OF THE NURSE STATION, SPRINKLERS ARE LOCATED TO HIGH. PIPE HANGERS MAY NEED TO BE ADJUSTED TO CORRECT THIS SITUATION.