Case: T08FR04274

Parcel: 110083070


Addresses:

4625 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - LIFE SAFETY

Case Number - T08FR04274

Inspection Description - INSP - LIFE SAFETY

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2009 INSP - LIFE SAFETY Approved
11/10/2008 INSP - LIFE SAFETY Correction Required DURING THE ANNUAL SPRINKLER INSPECTION (1-13-2008) THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) THE TAMPER SWITCH DID NOT ACTIVATE AND NEEDS TO BE REPAIRED

2) GUAGES AT THE RISER SHALL BE RECALIBRATED OR REPLACED AT 5 YEAR INTERVALS

3) SEVERAL SPRINKLER HEADS IN THE LOBBY NEED TO BE CLEANED. A SOFT BRUSH WILL AID IN THE CLEANING