Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04271
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2008 | INSP - FULL | Approved | ||
11/10/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFECIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE RISER IS DUE FOR THE FIVE YEAR INTERNAL INSPECTION. 2) THE SPARE HEAD BOX NEEDS AN ADDITIONAL UPRIGHT SPRINKLER HEAD. 3) PROVIDE SPRINKLER COVERAGE TO THE UNDERSIDE OF THE OVERHEAD DOORS IN THE BUICK REPAIR SHOP AT THE N. W. CORNER |