Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T08FR04270
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2008 | INSP - FULL | Correction Required | MET WITH MR. JEFF STEINER AT 4333 E. SPEEDWAY, DID A MAIN DRAIN FLOW ON THE SPRINKLER SYSTEM. CITY PRESSURE ON THE SYSYEM SIDE GUAGE WAS AT 95#. FLOWED APPROXMATELY FOR 5 MINUTES, PRESSURE ONLY DROPPED TO 75#, AND RETURNED TO 95# AT THE END OF FLOW TEST. IT APPEARS TO BE ONLY A GUAGE PROBLEM, SHOULD BE CLEARED WHEN THEY HAVE THE INTERNAL VALVE INSPECTION PERFORMED. |