Case: T08FR04270

Parcel: 12212043B


Addresses:

4333 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T08FR04270

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/10/2008 INSP - FULL Correction Required MET WITH MR. JEFF STEINER AT 4333 E. SPEEDWAY, DID A MAIN DRAIN FLOW ON THE SPRINKLER SYSTEM. CITY PRESSURE ON THE SYSYEM SIDE GUAGE WAS AT 95#. FLOWED APPROXMATELY FOR 5 MINUTES, PRESSURE ONLY DROPPED TO 75#, AND RETURNED TO 95# AT THE END OF FLOW TEST. IT APPEARS TO BE ONLY A GUAGE PROBLEM, SHOULD BE CLEARED WHEN THEY HAVE THE INTERNAL VALVE INSPECTION PERFORMED.