Case: T08FR04268

Parcel: 13502007C


Addresses:

1441 S WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04268

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2008 INSP - FULL Approved All violations have been corrected.
11/07/2008 INSP - FULL Violation 1) IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
A) Provide a cover for outlet in maintanence shop.
11/07/2008 INSP - FULL Violation 2) IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
A) You will mount your fire extinguisher in a conspicuous and accessible place on the wall.
11/07/2008 INSP - FULL Violation 3) IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.
A) you will secure compressed gas cylinder on N wall of 'mechanical' body stall.
11/07/2008 INSP - FULL Violation 4) IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
A) You will provide a hardwire with a GFCI to your waste paint " cooker" behind the mixing booth.
11/07/2008 INSP - FULL Violation 5) IFC 907.20.5 Maintenance, inspection and testing. The building owner shall be responsible for ensuring that the fire and life safety systems are maintained in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for maintaining, inspecting and testing such systems. A written record shall be maintained and shall be made available to the fire code official.
A) You will have your guage on your paint booth riser replaced.
B) You will have your 5 year test performed on your other riser per your sprinkler maintanence report.