Case: T08FR04251

Parcel: 11519007F


Addresses:

1855 W GRANT RD

Inspection Status: Correction Required

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Date Description Inspector Results Comments
11/07/2008 VIOL - HAZARDOUS MATERIALS,GEN Correction Required TFC 2703.5.1 Markings. Individual containers, cartons or packages
shall be conspicuously marked or labeled in an
approved manner.

_____1. All containers shall be labeled to identify it's contents.
11/07/2008 VIOL - HAZARDOUS MATERIALS,GEN Correction Required TFC 2703.5 Hazard identification signs. Unless otherwise
exempted by the fire code official, visible hazard identification
signs as specified in NFPA 704 for the specific material contained
shall be placed on stationary containers and
above-ground tanks and at entrances to locations where hazardous
materials are stored, dispensed, used or handled in
quantities requiring a permit and at specific entrances and locations
designated by the fire code official.

_____1. Hazard identification signs shall be placed on all entrance doors to the building and on the fence next to the southwest gate.

_____2. A hazard identification sign shall be placed on the propane storage cabinet located in the south yard.