Case: T08FR04242

Parcel: 108214430


Addresses:

1630 E RIVER RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/19/2009 INSP - FULL Approved
02/04/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 12-10-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 1630 E. RIVER. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
12/10/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE

1) MORGANCAIN & ASSOC. - 7, 155 DEGREE BRASS PENDANT AND 2, 155 DERGEE UPRIGHT SPRINKLER HEADS IN THE S. E. ROOM ARE PAINTED AND SHALL BE CHANGED OUT.
11/06/2008 INSP - FULL Correction Required SPRINKLER SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS. PLEASE FORWARD A REPORT OF COMPLETION WITH IN 30 DAYS.