Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04179
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2008 | INSP - FULL | Approved | ||
11/05/2008 | INSP - FULL | Correction Required | ACCORDING TO THE LAST FIRE SPRINKLER REPORT THIS OFFICE HAS RECEIVED, DATED MAY, 15, 2007, THE FOLLOWINF DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30. DAYS. IF THEY HAVE BEEN ADRESSED PLEASE FORWARD A COPY OF THE REPAIR MANIFEST TO THIS OFFICE. 1) REPLACE THE GASKET AT THE FIRE DEPARTMENT CONNECTION 2) 2ND. FLOOR TRAINING ROOM THERE ARE A PAIR OF SPRINKLER HEADS THAT ARE TO CLOSE TOGEATHER (4'). A BAFFEL MAY BE INSTALLED BETWEEN THEM 3) THE WATER MOTOR GONG WAS NOT FUNCTIONING AND NEEDS REPAIR |