Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04168
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2009 | INSP - FULL | Approved | APPROVED BY FIELD INSP. | |
04/17/2009 | INSP - FULL | Correction Required | DURING THE LAST FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTES WITHIN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) PRODUCE COOLER - TWO DRY PENDANT SPRINKLER HEADS THAT ARE CORRODED SHALL BE CHANGED OUT 2) GRILL AREA - THE THREE SPRINKLER HEADS THAT ARE LOADED WITH GREASE RESIDUE AND DUST SHALL BE CHANGED OUT. 3) DISH WASHING AREA - THREE SPRINKLER HEADS THAT ARE CORRODER SHALL BE CHANGED OUT. 4) NORTH DIN IN AREA - THE 5 DUST LOADED SPRINKLER HEADS MAY BE CLEANED WITH A SOFT BRUSH 5) SPRINKLER RISER - THE BOTTOM GUAGE IS BENT AT THE RISER NIPPLE AND SHALL BE CHANGED OUT. |
|
02/09/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. 1) PRODUCE COOLER - THE TWO CORRODED DRY PENDANT SPRINKLER HEADS SHALL BE CHANGED OUT. 2) GRILL AREA - THE PENDANT HEADS (3) THAT ARE LOADED WITH GREASE AND DUST SHALL BE CHANGED OUT. 3) DISHWASHING AREA - THE CORRODED SPRINKLER HEADS SHALL BE CHANGES OUT. 4) NORTH DINING AREA - THE SPRINKLER HEADS THAT ARE NEXT TO AIR DIFFUSERS SHALL BE CLEANED. 5) SPRINKLER RISER - THE BOTTOM GUAGE IS DAMAGED AND SHALL BE CHANGED OUT. |
|
11/04/2008 | INSP - FULL | Correction Required | SPRINKLER SYSTEMS ARE REQUIRED TO BE TESTED ANNUALY. WHERE AS THIS OFFICE DOES NOT HAVE A CURRENT REOPRT OF INSPECTION, A COPY SHALL BE PROVIDED THE FIRE PREVENTION OFFICE WITH IN 30 DAYS. |