Case: T08FR04150

Parcel: 10612017S


Addresses:

3544 N ROMERO RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/01/2008 INSP - FULL Approved
11/03/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE

1) SUITE 102 - THE SPRINKLER DROP AT THE OVERHEAD DOOR IS OUT OF ALIGNMENT AND HAS A DAMAGED DEFLECTOR AND SHALL BE REPAIRED

2) SUITE 112 - THE CEILING TILE IS SAGGING AND OBSTRUCTING THE SPRINKLER SPRAY PATTERN

3) THE SPARE HEAD BOX NEEDS 2, 155 DEGREE, TYCO SPRINKLER HEADS