Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2009 | INSP - FULL | Approved | PROPERTY IS NOW VACANT AND SECURED | |
| 11/03/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE PROVIDED THIS OFFICE 1) THE UPRIGHT SPRINKLER PROTECTION BELOW THE STAGE AREA ARE TO FAR OFF THE FRONT OF THE STAGE 2) OUTSIDE CANOPY, THE SPRINKLER HEAD ON THE EAST END EXCEEDS THE ALLOWABLE DISTANCE FOR CORRECT COVERAGE. 3) CHANGE OUT THE DAMAGED SPRINKLER HEAD IN THE MAIN ENTRANCE. 4) REPORT SHOWS CORRODED SPRINKLER HEADS IN THE WATER HEATER CLOSET AND OLD FREEZER, IF NECESSARY THEY SHALL BE CHANGED OUT. 5) THE BUTTERFLY INDICATOR ON THE CONTROL VALVE SHALL BE REPLACED 6) ALL STORAGE UNDER STAGE SHALL BE KEPT A MINIMUM OF 18 INCHES BELOW SPRINKLER HEAD DEFLECTORS |