Case: T08FR04134

Parcel: 12509005A


Addresses:

100 N TUCSON BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04134

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2008 INSP - FULL Approved
11/03/2008 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) THERE IS A PAINTED SPRINKLER HEAD UPRIGHT STANDARD, IN THE HALL BEHIND RECEPTION THAT NEEDS TO BE CHANGED OUT

2) THE HYDRAULIC CALCULATION PLATE AT THE RISER NEEDS THE REQUIRED INFORMATION

3) R. S. ENG. - A STANDARD UPRIGHT SPRINKLER HEAD IN THE SUPPLY ROOM IS IN THE VERTICLE POSITION, ROTATE PIPING TO THE CORRECT POSITION

4) R. S. ENG. - ABOVE THE FILE CABINETS, RELOCATE SPRINKLERS (3) THAT ARE AGAINST THE BAR JOIST, FOR CORRECT SPRAY PATTERN

5) PROVIDE SPRINKLER PROTECTION TO THE SHORT HALLWAY OUTSIDE OF THE QUALITY ASSURANCE OFFICE

6) BASEMENT, S. E. SERVER ROOM, ADJUST SPRINKLER HEAD AS NECESSARY AND PROVIDE AN ESCUTCHEON.

7) REPLACE THE MISSING CEILING TILE IN THE RED CROSS PHONE ROOM