Inspection Status: Violation
Inspection History: VIOL - INT.FINISH, DEC. MATL'S
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2008 | VIOL - INT.FINISH, DEC. MATL'S | Violation | TFC 807.1.2 Combustible decorative materials. The permissible amount of decorative materials meeting the flame propagation performance criteria of NFPA 701 shall not exceed 10 percent of the aggregate area of walls and ceilings. TFC 803.5.1 Textile wall coverings. Textile wall coverings shall comply with one of the following: 1. The coverings shall have a Class A flame spread index in accordance with ASTM E 84 *To qualify for the 10% coverage, approved documentation must be provided |
|
| 11/03/2008 | VIOL - INT.FINISH, DEC. MATL'S | Violation | TFC 803.5.1 Textile wall coverings. Textile wall coverings shall comply with one of the following: 1. The coverings shall have a Class A flame spread index in accordance with ASTM E 84 Provide documentation that the black draperies hanging @ rear of bldg are of approved materials Drapery materials @ ceiling are blocking the fire sprinkler coverage and must be removed prior to the business opening on Friday November 7, 2008. Failure to do so may result in a Citation being issued, possible closure and a probable fine. |